Blower Door and Duct Leakage Testing

Two fan tests measure how leaky the house and its ducts are, and the results go on a certificate posted at the electrical panel.

What the tests establish

The blower door test establishes how much air leaks through the house's envelope; the duct leakage test establishes how much air leaks out of the heating and cooling ducts. Both turn construction quality that nobody can see, the air sealing at top plates, penetrations and rim joists, and the sealing of duct joints, into numbers. That makes this stage unusual. Almost every other step in building a house is judged by looking at it before it is covered. This one is judged by measurement, and the measurement can be repeated at any time after move-in.

How the blower door test works

A calibrated fan is fitted into an exterior door and depressurizes the house to a standard test pressure of 50 pascals. The fan's airflow needed to hold that pressure is the leakage, in cubic feet per minute (CFM50). Divided by the house's volume and multiplied by 60, it becomes ACH50, air changes per hour at 50 pascals: how many times the house's air volume would be replaced each hour at that pressure.

Under the 2021 International Energy Conservation Code (IECC), no house under any compliance path may exceed 5.0 ACH50 (or 0.28 cfm per square foot of enclosure area). On the prescriptive path, the limit is 5.0 ACH50 in climate zones 0 through 2 and 3.0 ACH50 in zones 3 through 8. The 2012, 2015 and 2018 editions used 5 in zones 1 and 2 and 3 in zones 3 through 8. Which edition applies depends on what the city or state adopted.

How duct testing works

A smaller calibrated fan pressurizes the duct system, with registers sealed, to 25 pascals. Under the 2021 IECC, total leakage may not exceed 4.0 cubic feet per minute per 100 square feet of conditioned floor area, at rough-in with the air handler installed or after construction; 3.0 at rough-in without the air handler; and 8.0 where all ducts and the air handler are inside the thermal envelope. For a typical Texas house with ducts in a hot attic, every leak blows conditioned air into a space far hotter than the rooms it is meant to cool.

The certificate at the panel

The energy code requires a permanent certificate, completed by the builder or a registered design professional and posted on or in the electrical distribution panel (some adoptions allow the furnace or utility room). It lists the predominant insulation R-values, window U-factors and solar heat gain coefficients, and the results of the required envelope and duct leakage tests. Houston's adopted 2021 IECC requires it, and Dallas requires an energy code certificate to be submitted to the electrical inspector before final. For a buyer it is the single most useful energy document in the house, because it states the tested numbers rather than design intent.

Who does the testing

Some jurisdictions require an approved third party; the District of Columbia, for example, requires blower door and duct testing by an approved third-party energy testing professional. In much of Texas, testing is performed by energy raters engaged by the builder, sometimes as part of a HERS rating (Home Energy Rating System), which scores a house's modeled efficiency.

What the tests do not establish

They measure leakage, not where it is. A good ACH50 number does not mean insulation was installed well, and a passing duct test does not mean the ducts deliver the right airflow to each room. They are snapshots under test conditions, but they are honest ones, and they are repeatable.

Common mistakes

Testing before all penetrations are complete and never retesting, temporary sealing during the test that is removed afterward, and certificates left blank or posted with design values instead of test results. A buyer can compare the certificate with a retest by a qualified rater during the warranty year.

Where the rules come from

The 2021 limits are summarized in energy-inspector study material and the International Code Council's building tightness note; duct limits by Green Building Advisor. Houston's certificate rule is on its energy compliance certificate.

Frequently Asked Questions

What is a good ACH50 number for a new house?

The 2021 IECC caps every house at 5.0 ACH50 and sets 3.0 on the prescriptive path in climate zones 3 through 8. Lower means tighter. Your local code edition sets the applicable limit.

Where is the energy certificate in my house?

On or in the electrical panel in most adoptions; some allow it in the furnace or utility room.

Can I retest my house after move-in?

Yes. Blower door and duct leakage tests can be repeated by a qualified energy rater at any time.

Is a HERS rating the same as the code test?

No. A HERS rating models the house's overall efficiency and uses test results as inputs. The code tests are pass-or-fail limits.